CN

NPEXA-H511

Digital input isolated barrier, it converts switch or proximity detector signals (dry contact or NAMUR) from a hazardous area into relay signals to a safe area by isolation. The normal output sate and line fault detection function can be set with the DIP switch. It needs a backplane power supply. The input, output, and power supply are galvanically isolated from each other.

Input signal

Output signal

Channels

Power Supply Mode

LFD

Share
NPEXA-H511

【Core technology】

黄色底板安全栅.jpg

【Installation and disposal】



安全栅安装.gif安全栅拆卸.gif

                                    

Apparatus installation                            Apparatus disposal  




底板安装.gif底板拆卸.gif

 

Backplan installation                                Backplan disposal  




Supply
Power supply 18 ~ 32 V DC
Input
Input signal Dry contact or NAMUR
Output
Output signal Relay contact
Load capacity 0.5 A/35 V DC
General parameters
Switching trigger point Input signal > 2.1mA, signal “1”, the yellow LED is always bright; Input signal < 1.2mΑ, signal “0”, the yellow LED goes out
Relay mechanical life > 100000 switching cycles
Switch frequency < 10 Hz
DIP switch settings S1→a:output1 normal mode;S1→b:inverted mode;S2→a:LFD on;S2→b:LFD off
Energized/De-energized delay < 20 ms
Power dissipation ≤ 1.0 W
EMC data
Electromagnetic compatibility IEC 61326-3-1
Dielectric strength ≥ 2500V AC (intrinsically safe side / non-intrinsically safe side); ≥ 500V AC (Power supply /non-intrinsically safe side)
Insulation resistance ≥ 100 MΩ (Input /Output/Power supply)
Operating conditions
Operation temperature -20 ℃ ~ +60 ℃
Storage temperature -40 ℃ ~ +80 ℃
Suitable location Mounting in safe area, and connected to the intrinsic safety apparatus in hazardous area zone 0, zone 1, zone 2, ⅡA, ⅡB, ⅡC, T4 ~ T6
State
LFD function When input current ≤ 50μA, considers the input line breakdown, the output relay de-energized. If input current ≥ 6.5mA, considers the input circuit short-circuit, the output relay de-energized, the indicator red flashing
Mechanical specifications
Connection method Screw connection
Dimension 15.8mm (W) × 121.6mm (H) × 104.8mm (D)
Mounting type DIN35 mm
Certified data
Product approvals NEPSI, CE, FCC, CCC
Ex marking [Ex ia Ga]ⅡC
Um 250 V
Uo 10.5 V (Terminals 1, 2)
Io 11.3 mA (Terminals 1, 2)
Po 29.7 mW (Terminals 1, 2)
Co 0.97 μF (Terminals 1, 2)
Lo 100 mH (Terminals 1, 2)
NPEXA-C11

一入一出

热电偶输入安全栅