CN

NPEXA-H61P2

Frequency input isolated barrier, it converts the frequency signals from a hazardous area into 4~20mA signals to a safe area by isolation. It needs a backplane power supply. The input, output, and power supply are galvanically isolated from each other. Calibrate the apparatus or modify parameters by using a handheld programmer.

Input signal

Output signal

Channels

Power Supply Mode

Power Distribution

Share
NPEXA-H61P2

【Core technology】

黄色底板安全栅.jpg

【Installation and disposal】



安全栅安装.gif安全栅拆卸.gif

                                    

Apparatus installation                            Apparatus disposal  




底板安装.gif底板拆卸.gif

 

Backplan installation                                Backplan disposal  




Supply
Power supply 18 ~ 32 V DC
Input
Input signal frequency input, Max. input voltage: 30V, Min. input amplitude: 2V, frequency range: 0.1Hz~100kHz; PNP/NPN input, distribution voltage: 24V, current: ≤ 20mA, frequency range: 0.1Hz~10kHz; NAMUR input, distribution voltage: approx.8.2V, short-circuit current: approx.8mA, frequency range: 0.1Hz~10kHz
Output
Output signal 4 ~ 20 mA
Load resistance RL ≤ 500 Ω
Transfer characterisics
Accuracy ± 0.1 %F.S.
Temperature drift ≤ 0.01%F.S./℃
General parameters
Response time ≤ 500 ms
Power dissipation 0.8 W
EMC data
Electromagnetic compatibility IEC 61326-3-1
Dielectric strength ≥ 2500V AC (intrinsically safe side / non-intrinsically safe side); ≥ 500V AC (Power supply /non-intrinsically safe side)
Insulation resistance ≥ 100 MΩ (Input /Output/Power supply)
Operating conditions
Operation temperature -20 ℃ ~ +60 ℃
Storage temperature -40 ℃ ~ +80 ℃
Suitable location Mounting in safe area, and connected to the intrinsic safety apparatus in hazardous area zone 0, zone 1, zone 2, ⅡA, ⅡB, ⅡC, T4 ~ T6
State
Fault states Input signal state indicator (red), it is remain bright when input over-range. it is flicker when input breakage.
Mechanical specifications
Connection method Screw connection
Dimension 15.8mm (W) × 121.6mm (H) × 104.8mm (D)
Mounting type DIN35 mm
Certified data
Product approvals NEPSI, CE, FCC, CCC
Ex marking [Ex ia Ga]ⅡC
Um 250 V
Uo 10.5 V (Terminals 1, 2); 10.5 V (Terminals 5, 6); 28 V (Terminals 3, 4, 6)
Io 13 mA (Terminals 1, 2); 6 mA (Terminals 5, 6); 93 mA (Terminals 3, 4, 6)
Po 35 mW (Terminals 1, 2); 16 mW (Terminals 5, 6); 651 mW (Terminals 3, 4, 6)
Co 1.68 μF (Terminals 1, 2); 1.68 μF (Terminals 5, 6); 0.08 μF (Terminals 3, 4, 6)
Lo 100 mH (Terminals 1, 2); 700 mH (Terminals 5, 6); 4.2 mH (Terminals 3, 4, 6)
NPEXA-C11

一入一出

热电偶输入安全栅