CN

NPFR-H1D

Frequency input isolated barrier, it transfers the frequency signals from a hazardous area to a safe area. It needs a backplane power supply. The input, output, and power supply are galvanically isolated from each other.

Input signal

Output signal

Channels

Power Supply Mode

Power Distribution

Share
NPFR-H1D

【Core technology】

黄色底板温变.jpg

【Installation and disposal】



安全栅安装.gif安全栅拆卸.gif

                                    

Apparatus installation                            Apparatus disposal  




底板安装.gif底板拆卸.gif

 

Backplan installation                                Backplan disposal  





Supply
Power supply 18 ~ 32 V DC
Input
Input signal frequency input, Max. input voltage: 30V, Min. input amplitude: 2V, frequency range: 0.1Hz~100kHz; PNP/NPN input, distribution voltage: 12V or 24V, current: ≤ 20mA, frequency range: 0.1Hz~10kHz; NAMUR input, distribution voltage: approx.8.2V, short-circuit current: approx.8mA, frequency range: 0.1Hz~10kHz
Output
Output signal Open collector, high level: Vcc (≤ 30V), low level:≤ 2 V,drive current:≤ 10 mA;Emitter follower, high level:VCC - 2 V,low level:≤ 0.5 V,drive current:≤ 10 mA;Logic level , high level:18 V ≤ VH ≤ 24 V,low level:VL ≤ 2 V,Load resistance:≥ 2 kΩ
General parameters
Power dissipation 0.8 W
EMC data
Electromagnetic compatibility IEC 61326-3-1
Dielectric strength ≥ 1500 V AC (Input /Output); ≥ 500 V AC (Power supply /Output)
Insulation resistance ≥ 100 MΩ (Input /Output/Power supply)
Operating conditions
Operation temperature -20 ℃ ~ +60 ℃
Storage temperature -40 ℃ ~ +80 ℃
Mechanical specifications
Connection method Screw connection
Dimension 15.8mm (W) × 121.6mm (H) × 104.8mm (D)
Mounting type DIN35 mm
Certified data
Product approvals CE, FCC
NPEXA-C11

一入一出

热电偶输入安全栅