CN

NPGL-C744

This isolator transfers the CAN digital signals and provides isolated power supply for field devices. The input, output, and power supply are galvanically isolated from each other.

Input signal

Output signal

Channels

Power Supply Mode

Power Distribution

Share
NPGL-C744

Core technology

隔离C.png.jpg


【Installation and disposal】



C系列注塑外壳安装.gifC系列注塑外壳拆卸.gif

                                    

Installation                                               Disposal  




Supply
Power supply 18 ~ 60 V DC
Input signal CAN
Input
Distribution voltage Refer to rotary switch setting
Voltage tolerance ±10%
Output
Output signal CAN
Transmission delay ≤ 2 μs
Transmission rate ≤ 300 kbps
Drive nodes ≤ 10
General parameters
Rotary switch setting S0:5 V DC,100 mA;S1:6 V DC,100 mA;S2:8 V DC,50 mA;S4:9 V DC,50 mA;S8:12 V DC,50 mA
Power dissipation ≤ 2W (Distribution: 8V/9V/12V, 50mA); ≤ 4W (Distribution: 5V/ 6V, 100mA)
EMC data
Electromagnetic compatibility IEC 61326-3-1
Dielectric strength ≥ 1500V AC (Input /Output/Power supply)
Insulation resistance ≥ 100 MΩ (Input /Output/Power supply)
Operating conditions
Operation temperature -20 ℃ ~ +60 ℃
Storage temperature -40 ℃ ~ +80 ℃
Mechanical specifications
Connection method Screw connection
Dimension 17.8mm (W) × 110mm (H) × 117mm (D)
Mounting type DIN35 mm
Certified data
Product approvals CE, FCC
NPEXA-C11

一入一出

热电偶输入安全栅