CN

NPEXA-C11T1

Temperature input isolated barrier, it converts the thermocouple signals from a hazardous area into 4~20mA and RS485 signals to a safe area by isolation. It needs an independent power supply. The input, output, and power supply are galvanically isolated from each other. Calibrate the apparatus or modify parameters by using a handheld programmer.

Input signal

Output signal

Channels

Power Supply Mode

Share
NPEXA-C11T1

【Core technology】

安全栅C.png.jpg

【Installation and disposal】



C系列注塑外壳安装.gifC系列注塑外壳拆卸.gif

                                    

Installation                                               Disposal  






Supply
Power supply 18 ~ 60 V DC
Input
Input signal K, E, S, B, J, T, R, N, etc.
Output
Output signal Output1: 4 ~ 20mA; Output2: RS485
Load resistance RL ≤ 550 Ω
Communication parameters MODBUS-RTU, distance ≤ 1000m
Baud rate ≤ 19.2 kbps
Transfer characterisics
Conversion accuracy-E -100 ℃ ~ +1000 ℃/<300 ℃,±0.3 ℃/≥300 ℃,±0.1 %F.S.
Conversion accuracy-K -200 ℃ ~ +1372 ℃/<300 ℃,±0.3 ℃/≥300 ℃,±0.1 %F.S.
Conversion accuracy-J -100 ℃ ~ +1200 ℃/<300 ℃,±0.3 ℃/≥300 ℃,±0.1 %F.S.
Conversion accuracy-N -200 ℃ ~ +1300 ℃/<300 ℃,±0.3 ℃/≥300 ℃,±0.1 %F.S.
Conversion accuracy-S -50 ℃ ~ +1768 ℃/<500 ℃,±0.5 ℃/≥500 ℃,±0.1 %F.S.
Conversion accuracy-R -50 ℃ ~ +1768 ℃/<500 ℃,±0.5 ℃/≥500 ℃,±0.1 %F.S.
Conversion accuracy-T -20 ℃ ~ +400 ℃/<300 ℃,±0.3 ℃/≥300 ℃,±0.1 %F.S.
Conversion accuracy-B +400 ℃ ~ +1820 ℃/<500 ℃,±0.5 ℃/≥500 ℃,±0.1 %F.S.
Temperature drift 40 ppm/℃
General parameters
Compensation accuracy 1°C (Temperature compensation range: -20°C ~ +60°C)
Response time ≤ 500 ms
Power dissipation 0.9 W
EMC data
Electromagnetic compatibility IEC 61326-3-1
Dielectric strength ≥ 3000V AC (intrinsically safe side / non-intrinsically safe side) ≥ 1500V AC (Power supply /non-intrinsically safe side)
Insulation resistance ≥ 100 MΩ (Input /Output/Power supply)
Operating conditions
Operation temperature -20 ℃ ~ +60 ℃
Storage temperature -40 ℃ ~ +80 ℃
Suitable location Mounting in safe area, and connected to the intrinsic safety apparatus in hazardous area zone 0, zone 1, zone 2, ⅡA, ⅡB, ⅡC, T4 ~ T6
State
Output states Whatever input fault status (except breakage), the output follows the input within measuring range. And the maximum value would not exceed the 110% of the upper limit of the measuring range.
Mechanical specifications
Connection method Screw connection
Dimension 12.8mm (W) × 110mm (H) × 117mm (D)
Mounting type DIN35 mm
Certified data
Product approvals NEPSI, CE, FCC, CCC
Ex marking [Ex ia Ga]ⅡC
Um 250 V
Uo 8.7 V (Terminals 1, 2)
Io 33 mA (Terminals 1, 2)
Po 72 mW (Terminals 1, 2)
Co 5 μF (Terminals 1, 2)
Lo 28 mH (Terminals 1, 2)
NPPB-DIN Bus rail power supply
35mm standard rail
NPPB-BS210 I/O terminal base
Connect the rail BUS base, external power is introduced through the terminal block of the base. If a redundant power module is selected, this terminal can be left unselected.
NPPB-BSC028 Dust cover
Protect the exposed bus and split the combination as needed.
NPPB-SS5 Limiter
For fixed position, standard 2 sets
NPPB-TS35B Fixed piece
Material: metal iron, used for rail load-bearing reinforcement, standard 2 pieces
NPEXA-C11

一入一出

热电偶输入安全栅