CN

NPEXA-C277

Resistance input isolated barrier, it transfers the resistance signals from a hazardous area to a safe area. It needs an independent power supply. The input, output, and power supply are galvanically isolated from each other.

Input signal

Output signal

Channels

Power Supply Mode

Share
NPEXA-C277

【Core technology】

安全栅C.png.jpg

【Installation and disposal】



C系列注塑外壳安装.gifC系列注塑外壳拆卸.gif

                                    

Installation                                               Disposal  






Supply
Power supply 18 ~ 60 V DC
Input
Input signal 18 ~ 400 Ω
Line resistance ≤ 20 Ω per line
Output
Output signal 1 : 1
Exciting current 0.1 ~ 10 mA
Transfer characterisics
Conversion accuracy 0.5mA ~ 10mA excitation current,± 0.1%F.S. or < 0.2Ω(select max)
Temperature drift 30 ppm/℃
General parameters
Response time ≤ 500 ms
Power dissipation 0.4 W
EMC data
Electromagnetic compatibility IEC 61326-3-1
Dielectric strength ≥ 3000V AC (intrinsically safe side / non-intrinsically safe side); ≥ 1500V AC (Power supply /non-intrinsically safe side)
Insulation resistance ≥ 100 MΩ (Input /Output/Power supply)
Operating conditions
Operation temperature -20 ℃ ~ +60 ℃
Storage temperature -40 ℃ ~ +80 ℃
State
Output states Whatever input fault status (except breakage, breakage output about 16Ω,breakage output2 about 0V/mA), the output follows the input within measuring range. And output1 the maximum value would not exceed the upper limit 430Ω, output2 the maximum value would not exceed the 110% of the upper limit of the measuring range.
Mechanical specifications
Connection method Screw connection
Dimension 17.8mm (W) × 110mm (H) × 117mm (D)
Mounting type DIN35 mm
Certified data
Product approvals CNEX, CE, FCC, CCC
Ex marking [Ex ia Ga]ⅡC
Um 250 V
Uo 8.7 V (Terminals 1, 3; 2, 3)
Io 33 mA (Terminals 1, 3; 2, 3)
Po 72 mW (Terminals 1, 3; 2, 3)
Co 5 μF (Terminals 1, 3; 2, 3)
Lo 3 mH (Terminals 1, 3; 2, 3)
NPPB-DIN Bus rail power supply
35mm standard rail
NPPB-BS210 I/O terminal base
Connect the rail BUS base, external power is introduced through the terminal block of the base. If a redundant power module is selected, this terminal can be left unselected.
NPPB-BSC028 Dust cover
Protect the exposed bus and split the combination as needed.
NPPB-SS5 Limiter
For fixed position, standard 2 sets
NPPB-TS35B Fixed piece
Material: metal iron, used for rail load-bearing reinforcement, standard 2 pieces
NPEXA-C11

一入一出

热电偶输入安全栅