CN

NPEXA-CM31S1S

Analog input isolated barrier, it detects loop current and converts it from a hazardous area into 4~20mA(sink) signals to a safe area by isolation, and also provides transmitters with power in the hazardous area. It allows transmission of HART communication signals. The input, output, and power supply are galvanically isolated from each other.

Input signal

Output signal

Channels

Power Supply Mode

HART

Share
NPEXA-CM31S1S

【Core technology】

安全栅C.png.jpg

【Installation and disposal】



C系列注塑外壳安装.gifC系列注塑外壳拆卸.gif

                                    

Installation                                               Disposal  






Supply
Power supply 18 ~ 60 V DC
Input
Input signal 4 ~ 20mA, HART
Line resistance approx. 75Ω
Available voltage open-circuit voltage ≤ 26V; voltage: ≥ 16V at 20mA
Output
Output signal 4 ~ 20mA (Sink), HART
Load resistance RL < [(U-3)/0.02]Ω; U: Loop power supply
Transfer characterisics
Accuracy 0.1 %F.S.
Temperature drift 30 ppm/℃
General parameters
Response time ≤ 2 ms
Power dissipation 1.0 W
EMC data
Electromagnetic compatibility IEC 61326-3-1
Dielectric strength ≥ 3000V AC (intrinsically safe side / non-intrinsically safe side); ≥ 1500V AC (Power supply /non-intrinsically safe side)
Insulation resistance ≥ 100 MΩ (Input /Output/Power supply)
Operating conditions
Operation temperature -20 ℃ ~ +60 ℃
Storage temperature -40 ℃ ~ +80 ℃
Suitable location Mounting in safe area, and connected to the intrinsic safety apparatus in hazardous area zone 0, zone 1, zone 2, ⅡA, ⅡB, ⅡC, T4 ~ T6
Mechanical specifications
Connection method Screw connection
Dimension 12.8mm (W) × 110mm (H) × 117mm (D)
Mounting type DIN35 mm
Certified data
Product approvals NEPSI, CE, FCC, CCC
Ex marking [Ex ia Ga]ⅡC
Um 250 V
Uo 5 V (Terminals 1, 2); 28V (Terminals 2, 3)
Io 93 mA (Terminals 2, 3)
Po 651 mW (Terminals 2, 3)
Co 70 μF (Terminals 1, 2); 0.058 μF (Terminals 2, 3)
Lo 2.8 mH (Terminals 2, 3)
NPPB-DIN Bus rail power supply
35mm standard rail
NPPB-BS210 I/O terminal base
Connect the rail BUS base, external power is introduced through the terminal block of the base. If a redundant power module is selected, this terminal can be left unselected.
NPPB-BSC028 Dust cover
Protect the exposed bus and split the combination as needed.
NPPB-SS5 Limiter
For fixed position, standard 2 sets
NPPB-TS35B Fixed piece
Material: metal iron, used for rail load-bearing reinforcement, standard 2 pieces